Advantech ADAM-5080
4-ch Counter/Frequency Module
- Function Mode: Counter (Up/Down, Bi-direction) Frequency
- Input Frequency: Frequency Mode: 0.3~1000 Hz Counter Mode: 5000 Hz max.
- Minimum Pulse Width: 500μ sec. (Frequency Mode), 100μ sec. (Counter Mode)
- Isolated Voltage: 1000 VRMS
- Programmable Digital Noise Filter: 1~65000μ sec.
With ADAM-5080 4-Channel Counter/Frequency Module, users can select either counter or frequency mode for data input. ADAM-5080 offers users flexible and versatile applications such as counter, frequency, alarm setting, Up / Down or Bi-direction Functions.
General
- Certification
CE, FM
Connectors
1 x Plug-in screw terminal (# 14 ~ 22 AWG)
Enclosure
ABS+PC
Power Consumption
1.5 W (max.)
Counter/Frequency
- Counter Aux. Function
Initial preset, hi-low alarm setting, alarm digital output mapping, overflag
Channels
4
Input Frequency
0.3 ~ 1,000 Hz max. (frequency mode)
5,000 Hz max. (counter mode) TTL only
Input Level
Isolated or TTL level
Isolation Input Level
Logic level 0: 1 V DC max
Logic level 1: 3.5 ~ 30 V DC
Isolation Voltage
1,000 V RMS
Maximum Count
4,294,967,295 (32 bits)
Minimum Input Current
2 mA (isolated)
Minimum Pulse Width
500 μs (frequency mode)
100 μs (counter mode)
Modes
Counter (up/down, bi-direction), Frequency
Programmable Digital Filter
1 ~ 65,000 μsec (Noise Filter Function)
TTL Input Level
Logic level 0: 0 ~ 0.8 V DC
Logic level 1: 2.3 ~ 5 V DC
Note:
Does not support ADAM-5550 & 5560 Series